丁香花在线视频观看免费,GOGOGO高清免费完整版在线观看,日产中文字幕在线精品一区,在线看高H猛烈失禁潮喷

產(chǎn)品中心
ABCS-0.4無(wú)功動(dòng)態(tài)調(diào)節(jié)器(容性無(wú)觸點(diǎn)開關(guān))
ABCS-0.4無(wú)功動(dòng)態(tài)調(diào)節(jié)器(容性無(wú)觸點(diǎn)開關(guān))
產(chǎn)品分類:
產(chǎn)品簡(jiǎn)介:

ABCS 系列無(wú)功動(dòng)態(tài)調(diào)節(jié)器( 容性無(wú)觸點(diǎn)開關(guān)) 是電力電子產(chǎn)品可使用此產(chǎn)品將電力電容器負(fù)荷連接到電網(wǎng)。該產(chǎn)品專業(yè)用于需要安裝開關(guān)裝置和控制裝置的場(chǎng)合,可實(shí)現(xiàn)純電容或電抗( 最大到14%) 分步補(bǔ)償系統(tǒng)的快速投切。不僅可實(shí)現(xiàn)對(duì)稱三相電流的補(bǔ)償,也可以對(duì)電網(wǎng)進(jìn)行單相分步補(bǔ)償。

產(chǎn)品詳情
相關(guān)產(chǎn)品

參數(shù) Parameters

ABCS 系列無(wú)功動(dòng)態(tài)調(diào)節(jié)器( 容性無(wú)觸點(diǎn)開關(guān)) 是電力電子產(chǎn)品可使用此產(chǎn)品將電力電容器負(fù)荷連接到電網(wǎng)。該產(chǎn)品專業(yè)用于需要安裝開關(guān)裝置和控制裝置的場(chǎng)合,可實(shí)現(xiàn)純電容或電抗( 最大到14%) 分步補(bǔ)償系統(tǒng)的快速投切。不僅可實(shí)現(xiàn)對(duì)稱三相電流的補(bǔ)償,也可以對(duì)電網(wǎng)進(jìn)行單相分步補(bǔ)償。


技術(shù)數(shù)據(jù)

控制電路:

- 控制輸入:DC8-16V


負(fù)載電路:

- 供電電壓:Un400V 50Hz/60Hz

- 功耗:近似2W 每安培

- 負(fù)載容量:三相最大60kVar; 單相15kVar。


環(huán)境條件:

- 運(yùn)行溫度-20℃┄ +55℃

- 濕度: 非冷凝5% ┄ 95%

- 存儲(chǔ)溫度-25℃┄ +70℃


適用范圍:

- 額定電壓Un±10%

- 諧波電壓THDmax.5%

一次響應(yīng)速度:<20mS 連續(xù)響應(yīng)速度:<40mS


電氣安全:

- 保護(hù)級(jí)別Ⅰ

- 距離EN61010:2001 污染等級(jí)Ⅱ CAT Ⅲ

- 防護(hù)等級(jí)IP10


安裝:

- 安裝位置垂直或水平

- 散熱距離 距離通風(fēng)口最少50mm ,距離散熱裝置最少150mm

尺寸:116mm*187mm*170mm( 寬* 高* 深)

重量:近似2500g


The KCS series thyristor throw switch is a power electronics product that can be used to connect power capacitor loads to the grid. This product is specialized for applications requiring the installation of switching devices and control devices, and allows for the fast switching of pure capacitor or reactance (up to 14%) step-by-step compensation systems. It is possible to compensate not only symmetrical three-phase currents, but also single-phase step-by-step compensation of the grid.

Technical data

Control circuit: 

- Control input: DC8-16V

Load circuit: 

-Power supply voltage: Un400V 50Hz/60Hz

-Power consumption: approximate 2W per ampere

-Load capacity: Maximum 60kVar for three-phase; 15kVar for single-phase.

Applicable range: - Rated voltage Un±10%

-Harmonic voltage THDmax.5%

Primary response speed: <20mS Continuous response speed : <40mS

Electrical safety: 

-Protection level Ⅰ

-Distance EN61010:2001 pollution level II CAT III

-Protection class IP10

Environmental conditions: 

-Operating temperature -20℃┄ +55℃

-Humidity: non-condensing 5% ┄ 95%

-Storage temperature -25℃┄ +70℃

Installation: 

-Installation position vertical or horizontal

-Distance to heat dissipation Minimum 5 0 m m from the vent, minimum 1 5 0 m m from the heat sink

Size: 116mm*187mm*170mm(W*H*D)

Weight: approximate 2500g


安全事項(xiàng) Security matters

由于設(shè)計(jì)為風(fēng)扇散熱,必須保證空氣入口暢通,不能覆蓋散熱器出口。必須注意與附近元件的距離。對(duì)于額定負(fù)荷,新鮮空氣與排出空氣的溫度差會(huì)增加40℃。像電纜管道這樣的溫度敏感部件必須用套管保護(hù)起來(lái)。

必須在串聯(lián)斷路設(shè)備的條件下工作。

不能作為獨(dú)立的器件工作,必須在某個(gè)補(bǔ)償單元里使用。

必須在滿足使用條件的場(chǎng)合應(yīng)用。

甚至當(dāng)本投切開關(guān)按照規(guī)定條件使用時(shí),也不能避免本投切開關(guān)故障。在這種情況下,負(fù)載電路的電流和電壓都會(huì)受到影響。故障情形下,可能會(huì)發(fā)生下面的情況:電流中斷,半波運(yùn)行或持續(xù)能量流失。因此,在項(xiàng)目設(shè)計(jì)階段,要保證保護(hù)設(shè)備設(shè)計(jì)的正確性。

操作或接線錯(cuò)誤會(huì)導(dǎo)致設(shè)備或負(fù)載的損壞。

必須用帶有絕緣保護(hù)的電纜街頭連接。

此設(shè)備的安裝,維護(hù)和服務(wù)等工作必須由熟練的電工來(lái)操作完成。當(dāng)本投切開關(guān)連接到供電系統(tǒng)時(shí),容性負(fù)載( 電容) 將充電到電網(wǎng)電壓峰值。這就意味甚至當(dāng)開關(guān)斷開時(shí),負(fù)載仍是帶電的,依然連接在電網(wǎng)上。因此,當(dāng)安裝和維護(hù)工作進(jìn)行時(shí),在任何情況下,都必須

從電網(wǎng)斷開。否則有生命危險(xiǎn)!

從電網(wǎng)斷開后,容性負(fù)載中仍然有殘余電壓。在安裝和維護(hù)工作前,必須檢查電容器是否帶電。必須考慮電容器的放電時(shí)間。

在串聯(lián)電抗器時(shí),要充分考慮電網(wǎng)的復(fù)雜性,特別是針對(duì)固定次數(shù)的諧波信號(hào)進(jìn)行消諧時(shí),有可能會(huì)放大其他次數(shù)的諧波信號(hào),建議使用帶有諧波保護(hù)功能的無(wú)功補(bǔ)償控制器,否則會(huì)由于電荷傳導(dǎo)的影響而損壞本開關(guān)。

Reactive po wer dynamic r egulator (c apacitive non-contact swit ch)

Since the design is for fan cooling, the air inlet must be kept clear and must not cover the heat sink outlet. Attention must be paid to the distance from nearby components. For rated loads, the temperature difference between fresh air and exhaust air can increase by 40° C. Temperature sensitive components like cable ducts must be protected with sleeves.

Must work under the condition of a series break device.

Cannot work as a stand-alone device and must be used in some compensation unit.

Must be applied where the conditions of use are met.

Even when this throw switch is used according to the specified conditions, a failure of this throw switch cannot be avoided.

In this case, the current and voltage of the load circuit are affected. The following situations may occur in a fault situation: current interruption, half-wave operation or continuous energy loss. Therefore, during the design phase of the project, it is important to ensure that the protection equipment is designed correctly.

Operating or wiring errors can lead to damage to equipment or loads.

Street connections must be made with cables with insulation protection.

The installation, maintenance and service of this equipment must be performed by a skilled electrician. When this throw switch is connected to the power supply, the capacitive load (capacitor) is charged to the peak grid voltage. This means that even when the switch is disconnected, the load is still charged and connected to the grid. Therefore, when installation and maintenance work is carried out, it must be disconnected from the grid in all cases. Otherwise there is a risk to life!

After disconnection from the grid, there is still residual voltage in the capacitive load. Before installation and maintenance work, the capacitors must be checked for charging. The discharge time of the capacitor must be considered.

When connecting reactors in series, the complexity of the grid must be fully considered. Especially when detuning for a fixed number of harmonic signals, it is possible to amplify other numbers of harmonic signals and it is recommended to use a reactive power compensation controller with harmonic protection, otherwise this switch can be damaged due to the influence of charge conduction.


應(yīng)用 Applications

本投切開關(guān)特別適合應(yīng)用在頻率和無(wú)功快速變化的負(fù)荷。與傳統(tǒng)技術(shù)相比本開關(guān)的優(yōu)點(diǎn)是:

- 投切速度快- 投切對(duì)系統(tǒng)污染小

- 投切時(shí)沒(méi)有磨損部件- 使用壽命長(zhǎng),操作頻率不受限

應(yīng)用領(lǐng)域:

- 起重機(jī)設(shè)備 - 提升機(jī) - 焊接設(shè)備 - 制模 - 風(fēng)力輪機(jī)

本投切開關(guān)可以與無(wú)功控制器,可編程控制器,計(jì)算機(jī)系統(tǒng)和過(guò)程控制單元配合工作。

This throw switch is particularly suitable for applications with rapidly changing loads in terms of frequency and reactive power. The advantages of this switch compared to conventional technology are:

-Fast switching speed -Low pollution of the system during switching

-No wear parts during switching - Long service life and unlimited operating frequency

Application areas:

-Crane equipment -Lifters -Welding equipment -Molding -Wind turbines

This throw switch can work with reactive power controllers, programmable controllers, computer systems and process control units.


安裝 Installation

本投切開關(guān)可以水平或垂直安裝。由于強(qiáng)制散熱,所有產(chǎn)生的暖空氣幾乎從一個(gè)方向排出。在最大負(fù)荷下,預(yù)計(jì)有最大40K 的溫升。

如果系統(tǒng)中有溫度敏感元件,像電纜管道,就必須用套管保護(hù)起來(lái)。

扇側(cè):>50mm 散熱出口:>150mm

如果垂直安裝,必須保證散熱空氣從上面排出。注意:垂直安裝時(shí),應(yīng)防止異物掉入散熱器中而導(dǎo)致風(fēng)機(jī)損壞,所以在安裝時(shí)須用防護(hù)板之類的物品將散熱器罩住,在測(cè)試和運(yùn)行前再將防護(hù)板拆除。

This throw switch can be installed horizontally or vertically. Due to forced heat dissipation, all generated warm air is discharged from almost one direction. At maximum load, a temperature rise of up to 40 K is expected. If there are temperature sensitive elements in the system, like cable ducts, they must be protected with sleeves.

Fan side: >50 mm Heat dissipation outlet: >150 mm

If installed vertically, it must be ensured that the cooling air is discharged from above. Note: When installed vertically, foreign objects should be prevented from falling into the radiator and causing damage to the fan, so the radiator must be covered with a protective plate or something like that during installation, and then removed before testing and operation.


1.jpg


2.jpg


3.jpg

亚洲国产另类久久久精品黑人| 国产精品沙发午睡系列999| 亚洲A∨无码一区二区三区| 免费看国产成年无码AV| 永久AV狼友网站在线观看| 亚洲AⅤ天堂AV天堂无码麻豆|